Science  People  Locations  Timeline
Index: A B C D E F G H I J K L M N O P Q R S T U V W X Y Z

Home > Three-phase electric power


 Contents
Three-phase is a common method of electric power transmission in industrialised countries. It is a type of polyphase system.

The three phases are typically labelled by colors which vary by country. In the UK they were traditionally red, yellow and blue but it is in the process of harmonising to brown black and grey right now (april 2004-april 2006 window). In the USA they are black, red and blue. The current European standard is brown, black and grey but this is a very recent introduction. Brown and two blacks was common in Europe before and other combinations were in use before that.

Three phase systems may or may not have a neutral core. The advantage of having one is it allows a higher voltage to be used for the three phase system whilst supporting the lower voltage of single phase appliances. However in high voltage distribution situations it is common not to have a neutral as the loads can simply be connected phase-phase (and they have to be designed for the high voltage system anyway) __TOC__

1 Generation and Distribution

At the power station an electrical generator converts mechanical power into a set of alternating electric currents, one from each electromagnetic coil or winding of the generator. The currents are sinusoidal functions of time, all at the same frequency but with different phases. In a three-phase system the phases are spaced equally, separated from each other by 120° (which is the maximum phase separation possible). The frequency is typically 50  Hz in Europe and 60 Hz in the US (see List of countries with mains power plugs, voltages & frequencies).

Generators output at a voltage that ranges from hundreds of volts up to 30,000 volts. This voltage is usually "stepped-up" to a higher voltage with a transformer. The reason the voltage is increased is to reduce losses. Power essentially is equal to the product of voltage and current - so as you increase the voltage, you will reduce the current for a given value of power. Heating losses in a transmission line are proportional to the square of the current so if you can halve the current in a line, you will reduce the losses by four. For this reason some transmission lines operate at voltages in excess of 500,000 volts.

Generally voltage is changed several times during distriburion being changed up on the way to the grid main lines and down again from there to the destination.

At the destination, a transformer supplies the power stepped down from the high-voltage transmission line to three sinusoidally varying electric currents of 120  V (in the US) or 230 V (in Europe) alternating current (Vac). Including the neutral this gives four conductors. This may be split out into single phase service cables through joints in the supply network or it may be delivered to a master distribution board (breaker panel) at the customer's premises. Connecting an electrical circuit from one phase to the neutral supplies the countries standard single phase voltage (120 Vac or 230 Vac) to the circuit.

The power transmission grid is organised so that each phase carries the same magnitude of current out of the major parts of the transmission system. The currents returning from the customers' premises to the last supply transformer all share the neutral wire, but the three-phase system ensures that the sum of the returning currents is approximately zero. The delta wiring of the primary side of that supply transformer means that no neutral is needed in the high voltage side of the network.

2 Connecting Phase-Phase

Connecting between two phases provides √3 or 173% of the single-phase voltage (208 Vac in US; 400 Vac in Europe) because the out-of-phase waveforms add to provide a higher peak voltage in the resulting waveform. Such connection is referred to as a line to line connection and is usually done with a two pole circuit breaker. This kind of connection is used a lot for heaters in america, such as, for example, a 2kW, 208 volt baseboard heater.



Read more »

Non User